Marking ATEX: II 2G Ex eb 60079-30-1, IIC T3, T4, T5, T6 Gb IECEx: Ex eb 60079-30-1, IIC T3, T4, T5, T6 Gb
Ambient Temperature -60 °C < Ta < +160 °C
Certification
II 2D Ex tb 60079-30-1, IIIC T170 °C, T135 °C, T95 °C, T80 °C Db
Ex tb 60079-30-1, IIIC T170 °C, T135 °C, T95 °C, T80 °C Db
The PLEXO TCS connection system can be used for BARTEC self-regulating heating cables. This modular connection technology enables the simple and reliable assembly of supply connections, splicing and remote-end terminations.
PLEXO TCS is plugged and built up with a patented sealing and clamping technology. Maintenance work and later modifications on the heating circuit can be performed quickly and flexibly. The strands from the heating cable or the supply cable are fixed in place securely using the spring-loaded terminals in the internal clamping technology.
Technical Data
| Rated voltage | max. 277 V |
|---|---|
| Max. breaker rating | PSB / MSB / HSB / HSB+ : 32A, C-Characteristic |
| Protection class | EN 60079-0: IP 65 EN 60529: IP 66/IP 68 |
| Service temperature range | -60 °C up to +160 °C |
| Rated cross-section | max. 4 mm² |
| Min. installation temperature | -55 °C |
| Cold cable diameter range | 9 mm DA ≤ 10 mm 10 mm DA ≤ 12 mm 12 mm DA ≤ 14 mm 14 mm DA ≤ 16 mm |
Manuals/Operating Instructions/Guides
- DE
- EN
- RU
Declarations
- DE
- EN
- FR
Data Sheets