Marking

N/A

Ambient Temperature

Ambient temperature
0 °C to +60 °C

Certification

EU Declaration of Conformity
  • DE
  • EN
  • FR

The system detects even small liquid leaks quickly and reliably.
There is an optical and acoustic alarm signal.
At the same time potential-free contacts are set for signals to the building services management and control tasks.
The max. monitoring length is 1000 m. Up to 50 point sensors can be installed.

Technical Data

Protection class IP 54
Structure Wall-mounted enclosure with membrane keyboard and separate terminal area
Dimensions 166 x 160 x 84 mm (W x H x D)
Sensitivity Response sensitivity adjustable
Display optical: LED displays operation/alarm/rupture
acoustic: piezoelectric buzzer
Keyboard two-stage confirm button (stage 1: buzzer off); on/off button
Memory alarm/rupture relay memory
Connection Inputs:
– voltage supply AC 230 V/50 to 60 Hz/5.3 VA or DC 24 V/1.3 W as standard
– sensor via two-wire lead (sensor cable length max. 1000 m)
– point sensors max. quantity of 50
Outputs:
– alarm relay, two separate change-over contacts
(6 A at AC 230 V/6 A at DC 24 V)
– rupture/power failure relay, 1 change-over contact in fail safe function (6 A at AC 230 V/6 A at DC 24 V)