Marking ATEX: IECEx:
Ambient Temperature Operating temperature Storage temperature Certification ATEX Zone 1/21
Ex II 3G Ex ec mc ic [ic pzc] IIC T4 Gb
Ex II 3D Ex tc [ic pzc] IIIC T130 °C Db
Ex ec mc ic [ic pzc] IIC T4 Gb
Ex tc [ic pzc] IIIC T130 °C Db
-25 °C to +50 °C @ T4
(-13 °F to 140 °F @ T4)
-20 °C to +60 °C
(-4 °F to 140 °F)
DE
EN
IECEx Zone 1/21
EN
EAC
RU
CCC
ZH
ZH
The SILASmv Ex p control unit controls and monitors the purge and operating phase of small, separate, pressurised enclosure equipment protected in accordance with ignition protection type pzc. The parameters can be set using the integrated WEB interface or the optionally available p operator panel. The SILASmv features two release relays; one which is energised and one which has floating contacts. Two signal relays with one changeover contact each are additionally available. Three PT100/1000 inputs are available to monitor the temperature of the Ex p-protected equipment. Up to three switch values can be assigned to them. The design of the SILASmv means that all components required for the pressurised enclosure are located in the control unit. The equipment to be monitored is connected to the Ex p control unit by means of a pipe, which allows a maximum purge volume of 70 litres.
The following components can also be connected: There is the option to connect a p operator panel
Technical Data
| Protection class | IP 66 according to EN/IEC 60529 IP 64 according to EN/IEC 60079-0 |
|---|---|
| Pressure range | 0 to 25 mbar for all pressure switching levels |
| Purge time | 0 to 120 minutes (adjustable) |
| Temperatures | Operating temperature -25 °C to +60 °C @ T4 (-13 °F to 140 °F @ T4) -25 °C to +50 °C @ T5 (-13 °F to 104 °F @ T5) Storage temperature -20 °C to +60 °C (-4 °F to 140 °F) |
| Voltage | AC Variant: AC 100 V up to 230 V DC Variant: DC 24 V up to 44 V |
| Material | V4A stainless steel |
| Display | 6 LEDs for status display |
| Relay | Enable contact, switched input voltage max. load 5A Enable relay, potentiel free, 4 NO 2x Signal relay for status transmission (potentail free), CO |
| Weight | 9.8 kg |
Manuals/Operating Instructions/Guides
Operating Instructions – SILASmv control unit
- DE
- EN
Declaration
EU-Declaration of Conformity – 01-37A2-7C0001
- DE
- EN
- FR
Data Sheets
Data Sheet – SILASmv control unit